Experimental assessment of an absorption cooling system operating with the ammonia/lithium nitrate mixture Article uri icon

abstract

  • This paper reports the experimental results of a single effect absorption cooling system of 3kW of nominal cooling capacity operating with ammonia-lithium nitrate solution. The system was designed and built in the Instituto de Energías Renovables of the Universidad Nacional Autónoma de México and can be used for food conservation or air conditioning. The absorber and generator are falling film heat exchangers. The condenser, evaporator and solution heat exchanger are compact plate heat exchangers. The heat was supplied to the generator at temperatures between 85°C and 105°C, while the cooling water temperatures to remove the heat produced during the condensation and absorption varied between 18°C and 36°C. The results showed that the system can produce up to 2.7kW of cooling capacity at heating water temperatures of 95°C and can achieve evaporator temperatures as low as 1°C. The experimental coefficients of performance varied between 0.45 and 0.70. Because of the developed system do not need a rectifier and reasonable good coefficients of performance were achieved, the developed system seems to be a good alternative to be used for food conservation or air conditioning. © 2014 Elsevier Ltd.

publication date

  • 2014-01-01

published in