abstract
This paper shows how a single phase STATCOM model can be seen as a two block series connection. In this way, it is suitable to use a cascade control in order to regulate both DC links voltages and reactive power needed by AC main. This last is achieved through control strategy consisting in two parts: one of them is a cascade multi-loop control which delivers only one average control signal and the other part consists of adjustment mechanism which calculates the deviations from average control signal allowing generating the control signals for each cell. Tuning of cascade control is treated. In this case STATCOM is based on an asymmetrical multilevel converter. In order to verify the control strategy simulation and experimental results are presented. © 2010 IEEE.
publication date
published in
Research
keywords
Adjustment mechanisms; Cascade control; Control signal; Control strategies; DC links; Multi-loop control; Multilevel converter; Series connections; Single phase; Statcom; Cascade control systems; DC power transmission; Industrial electronics